2/0 AWG wire size

2/0 AWG wire is 9.27 mm (0.365 in) in diameter with a cross section of 67.4 mm². The closest metric size is 70 mm².

2/0 AWG specifications

Diameter9.27 mm · 0.365 in
Cross section67.4 mm²
Circular mils133 kcmil
Copper resistance0.256 Ω/km · 0.0779 Ω/1000 ft
Aluminium resistance0.418 Ω/km
Nearest metric size70 mm²

Solid conductor, copper at 20 °C. Values from the standard AWG formula.

Voltage drop example

At 100 A over a 10 m run (there and back), 2/0 AWG copper drops about 0.511 V.

That is 0.222% of 230 V or 0.426% of 120 V. Many guides aim for under 3%. For your own length and current, use the wire gauge calculator.

What is 2/0 AWG wire used for?

2/0 AWG is commonly used for large feeders, service entrance conductors, welding leads and battery cables.

Always size wire from your local electrical code and the cable maker’s current rating, which depend on insulation, installation method and temperature. The figures on this page describe the conductor itself.

How does 2/0 AWG compare with nearby sizes?

The next thicker size is 3/0 AWG at 85 mm². The next thinner size is 1/0 AWG at 53.5 mm². Every 3 gauge steps roughly halves or doubles the cross section, and every 6 steps roughly halves or doubles the diameter.

Questions about 2/0 AWG

What is 2/0 AWG in mm²?

2/0 AWG has a cross section of 67.4 mm², from a diameter of 9.27 mm. The nearest standard metric cable that is at least as large is 70 mm².

What is the diameter of 2/0 AWG wire?

A solid 2/0 AWG conductor is 9.27 mm, or 0.365 inches, across. Stranded wire of the same gauge is slightly larger overall.

What is the resistance of 2/0 AWG copper wire?

About 0.256 ohms per kilometre (0.0779 ohms per 1000 ft) for annealed copper at 20 °C. Aluminium of the same size is about 0.418 ohms per kilometre.