AWG wire size chart

American Wire Gauge runs from 4/0 (11.7 mm, 107 mm²) down to 40 AWG (0.08 mm). A smaller number means a thicker wire; every 3 steps roughly doubles the cross section.

Pick a size for full details, or use the wire gauge calculator for voltage drop.

AWGDiameter (mm)Diameter (in)Area (mm²)kcmilCopper Ω/kmCopper Ω/1000 ft
4/0 11.70.461072120.1610.049
3/0 10.40.41851680.2030.0618
2/0 9.270.36567.41330.2560.0779
1/0 8.250.32553.51060.3220.0983
1 7.350.28942.483.70.4070.124
2 6.540.25833.666.40.5130.156
3 5.830.22926.752.60.6460.197
4 5.190.20421.241.70.8150.248
5 4.620.18216.833.11.030.313
6 4.120.16213.326.31.30.395
7 3.660.14410.520.81.630.498
8 3.260.1288.3716.52.060.628
9 2.910.1146.6313.12.60.792
10 2.590.1025.2610.43.280.999
11 2.30.09074.178.234.131.26
12 2.050.08083.316.535.211.59
13 1.830.0722.625.186.572
14 1.630.06412.084.118.282.53
15 1.450.05711.653.2610.43.18
16 1.290.05081.312.5813.24.02
17 1.150.04531.042.0516.65.06
18 1.020.04030.8231.6220.96.38
19 0.9120.03590.6531.2926.48.05
20 0.8120.0320.5181.0233.310.2
21 0.7230.02850.410.814212.8
22 0.6440.02530.3260.6425316.1
23 0.5730.02260.2580.50966.820.4
24 0.5110.02010.2050.40484.225.7
25 0.4550.01790.1620.3210632.4
26 0.4050.01590.1290.25413440.8
27 0.3610.01420.1020.20216951.5
28 0.3210.01260.0810.1621364.9
29 0.2860.01130.06420.12726881.8
30 0.2550.010.05090.101339103
31 0.2270.008930.04040.0797427130
32 0.2020.007950.0320.0632538164
33 0.180.007080.02540.0501679207
34 0.160.00630.02010.0398856261
35 0.1430.005610.0160.03151,080329
36 0.1270.0050.01270.0251,360415
37 0.1130.004450.010.01981,720523
38 0.1010.003970.007970.01572,160660
39 0.08970.003530.006320.01252,730832
40 0.07990.003140.005010.009893,4401,050

Questions about wire gauges

What does AWG mean?

AWG stands for American Wire Gauge, the standard used in North America for the diameter of round, solid, non-ferrous wire. A smaller number means a thicker wire.

How do I convert AWG to mm²?

Find the diameter with d = 0.127 mm × 92^((36 − n) / 39), then the area is π/4 × d². For example 12 AWG is 2.05 mm across, which gives 3.31 mm².

Why does a smaller AWG number mean thicker wire?

The numbers come from how many drawing steps were needed to make the wire. Thinner wire went through more dies, so it got a higher number.

Solid copper at 20 °C. Current ratings depend on insulation, installation and local code, so they are not listed here.