4 AWG wire size
4 AWG wire is 5.19 mm (0.204 in) in diameter with a cross section of 21.2 mm². The closest metric size is 25 mm².
4 AWG specifications
| Diameter | 5.19 mm · 0.204 in |
|---|---|
| Cross section | 21.2 mm² |
| Circular mils | 41.7 kcmil |
| Copper resistance | 0.815 Ω/km · 0.248 Ω/1000 ft |
| Aluminium resistance | 1.33 Ω/km |
| Nearest metric size | 25 mm² |
Solid conductor, copper at 20 °C. Values from the standard AWG formula.
Voltage drop example
At 50 A over a 10 m run (there and back), 4 AWG copper drops about 0.815 V.
That is 0.354% of 230 V or 0.679% of 120 V. Many guides aim for under 3%. For your own length and current, use the wire gauge calculator.
What is 4 AWG wire used for?
4 AWG is commonly used for feeders to subpanels, large appliances and inverter or battery cables.
Always size wire from your local electrical code and the cable maker’s current rating, which depend on insulation, installation method and temperature. The figures on this page describe the conductor itself.
How does 4 AWG compare with nearby sizes?
The next thicker size is 3 AWG at 26.7 mm². The next thinner size is 5 AWG at 16.8 mm². Every 3 gauge steps roughly halves or doubles the cross section, and every 6 steps roughly halves or doubles the diameter.
Questions about 4 AWG
What is 4 AWG in mm²?
4 AWG has a cross section of 21.2 mm², from a diameter of 5.19 mm. The nearest standard metric cable that is at least as large is 25 mm².
What is the diameter of 4 AWG wire?
A solid 4 AWG conductor is 5.19 mm, or 0.204 inches, across. Stranded wire of the same gauge is slightly larger overall.
What is the resistance of 4 AWG copper wire?
About 0.815 ohms per kilometre (0.248 ohms per 1000 ft) for annealed copper at 20 °C. Aluminium of the same size is about 1.33 ohms per kilometre.