10 AWG wire size
10 AWG wire is 2.59 mm (0.102 in) in diameter with a cross section of 5.26 mm². The closest metric size is 6 mm².
10 AWG specifications
| Diameter | 2.59 mm · 0.102 in |
|---|---|
| Cross section | 5.26 mm² |
| Circular mils | 10.4 kcmil |
| Copper resistance | 3.28 Ω/km · 0.999 Ω/1000 ft |
| Aluminium resistance | 5.36 Ω/km |
| Nearest metric size | 6 mm² |
Solid conductor, copper at 20 °C. Values from the standard AWG formula.
Voltage drop example
At 20 A over a 10 m run (there and back), 10 AWG copper drops about 1.31 V.
That is 0.57% of 230 V or 1.09% of 120 V. Many guides aim for under 3%. For your own length and current, use the wire gauge calculator.
What is 10 AWG wire used for?
10 AWG is commonly used for dedicated circuits for water heaters, dryers and air conditioners.
Always size wire from your local electrical code and the cable maker’s current rating, which depend on insulation, installation method and temperature. The figures on this page describe the conductor itself.
How does 10 AWG compare with nearby sizes?
The next thicker size is 9 AWG at 6.63 mm². The next thinner size is 11 AWG at 4.17 mm². Every 3 gauge steps roughly halves or doubles the cross section, and every 6 steps roughly halves or doubles the diameter.
Questions about 10 AWG
What is 10 AWG in mm²?
10 AWG has a cross section of 5.26 mm², from a diameter of 2.59 mm. The nearest standard metric cable that is at least as large is 6 mm².
What is the diameter of 10 AWG wire?
A solid 10 AWG conductor is 2.59 mm, or 0.102 inches, across. Stranded wire of the same gauge is slightly larger overall.
What is the resistance of 10 AWG copper wire?
About 3.28 ohms per kilometre (0.999 ohms per 1000 ft) for annealed copper at 20 °C. Aluminium of the same size is about 5.36 ohms per kilometre.