16 AWG wire size

16 AWG wire is 1.29 mm (0.0508 in) in diameter with a cross section of 1.31 mm². The closest metric size is 1.5 mm².

16 AWG specifications

Diameter1.29 mm · 0.0508 in
Cross section1.31 mm²
Circular mils2.58 kcmil
Copper resistance13.2 Ω/km · 4.02 Ω/1000 ft
Aluminium resistance21.5 Ω/km
Nearest metric size1.5 mm²

Solid conductor, copper at 20 °C. Values from the standard AWG formula.

Voltage drop example

At 5 A over a 10 m run (there and back), 16 AWG copper drops about 1.32 V.

That is 0.573% of 230 V or 1.1% of 120 V. Many guides aim for under 3%. For your own length and current, use the wire gauge calculator.

What is 16 AWG wire used for?

16 AWG is commonly used for extension cords, lamp cords, speaker wire and low voltage control wiring.

Always size wire from your local electrical code and the cable maker’s current rating, which depend on insulation, installation method and temperature. The figures on this page describe the conductor itself.

How does 16 AWG compare with nearby sizes?

The next thicker size is 15 AWG at 1.65 mm². The next thinner size is 17 AWG at 1.04 mm². Every 3 gauge steps roughly halves or doubles the cross section, and every 6 steps roughly halves or doubles the diameter.

Questions about 16 AWG

What is 16 AWG in mm²?

16 AWG has a cross section of 1.31 mm², from a diameter of 1.29 mm. The nearest standard metric cable that is at least as large is 1.5 mm².

What is the diameter of 16 AWG wire?

A solid 16 AWG conductor is 1.29 mm, or 0.0508 inches, across. Stranded wire of the same gauge is slightly larger overall.

What is the resistance of 16 AWG copper wire?

About 13.2 ohms per kilometre (4.02 ohms per 1000 ft) for annealed copper at 20 °C. Aluminium of the same size is about 21.5 ohms per kilometre.