17 AWG wire size
17 AWG wire is 1.15 mm (0.0453 in) in diameter with a cross section of 1.04 mm². The closest metric size is 1.5 mm².
17 AWG specifications
| Diameter | 1.15 mm · 0.0453 in |
|---|---|
| Cross section | 1.04 mm² |
| Circular mils | 2.05 kcmil |
| Copper resistance | 16.6 Ω/km · 5.06 Ω/1000 ft |
| Aluminium resistance | 27.2 Ω/km |
| Nearest metric size | 1.5 mm² |
Solid conductor, copper at 20 °C. Values from the standard AWG formula.
Voltage drop example
At 5 A over a 10 m run (there and back), 17 AWG copper drops about 1.66 V.
That is 0.722% of 230 V or 1.38% of 120 V. Many guides aim for under 3%. For your own length and current, use the wire gauge calculator.
What is 17 AWG wire used for?
17 AWG is commonly used for extension cords, lamp cords, speaker wire and low voltage control wiring.
Always size wire from your local electrical code and the cable maker’s current rating, which depend on insulation, installation method and temperature. The figures on this page describe the conductor itself.
How does 17 AWG compare with nearby sizes?
The next thicker size is 16 AWG at 1.31 mm². The next thinner size is 18 AWG at 0.823 mm². Every 3 gauge steps roughly halves or doubles the cross section, and every 6 steps roughly halves or doubles the diameter.
Questions about 17 AWG
What is 17 AWG in mm²?
17 AWG has a cross section of 1.04 mm², from a diameter of 1.15 mm. The nearest standard metric cable that is at least as large is 1.5 mm².
What is the diameter of 17 AWG wire?
A solid 17 AWG conductor is 1.15 mm, or 0.0453 inches, across. Stranded wire of the same gauge is slightly larger overall.
What is the resistance of 17 AWG copper wire?
About 16.6 ohms per kilometre (5.06 ohms per 1000 ft) for annealed copper at 20 °C. Aluminium of the same size is about 27.2 ohms per kilometre.