34 AWG wire size
34 AWG wire is 0.16 mm (0.0063 in) in diameter with a cross section of 0.0201 mm².
34 AWG specifications
| Diameter | 0.16 mm · 0.0063 in |
|---|---|
| Cross section | 0.0201 mm² |
| Circular mils | 0.0398 kcmil |
| Copper resistance | 856 Ω/km · 261 Ω/1000 ft |
| Aluminium resistance | 1,400 Ω/km |
| Nearest metric size | No standard metric cable this size |
Solid conductor, copper at 20 °C. Values from the standard AWG formula.
Voltage drop example
At 0.5 A over a 10 m run (there and back), 34 AWG copper drops about 8.56 V.
That is 3.72% of 230 V or 7.13% of 120 V. Many guides aim for under 3%. For your own length and current, use the wire gauge calculator.
What is 34 AWG wire used for?
34 AWG is commonly used for fine electronics, ribbon cables, headphone leads and magnet wire for coils.
Always size wire from your local electrical code and the cable maker’s current rating, which depend on insulation, installation method and temperature. The figures on this page describe the conductor itself.
How does 34 AWG compare with nearby sizes?
The next thicker size is 33 AWG at 0.0254 mm². The next thinner size is 35 AWG at 0.016 mm². Every 3 gauge steps roughly halves or doubles the cross section, and every 6 steps roughly halves or doubles the diameter.
Questions about 34 AWG
What is 34 AWG in mm²?
34 AWG has a cross section of 0.0201 mm², from a diameter of 0.16 mm.
What is the diameter of 34 AWG wire?
A solid 34 AWG conductor is 0.16 mm, or 0.0063 inches, across. Stranded wire of the same gauge is slightly larger overall.
What is the resistance of 34 AWG copper wire?
About 856 ohms per kilometre (261 ohms per 1000 ft) for annealed copper at 20 °C. Aluminium of the same size is about 1,400 ohms per kilometre.